What Is Kv Value? Metric Flow Coefficient
Definition and Formula
| Parameter | Symbol | Unit |
|---|---|---|
| Flow coefficient (metric) | Kv | m3/h at 1 bar delta-P (water, 5-30 degC) |
| Flow rate | Q | Cubic meters per hour (m3/h) |
| Pressure drop | delta-P | bar (P1 - P2) |
| Specific gravity | G | Relative to water (water = 1.0) |
Liquid flow formula:
Kv = Q x sqrt(G / delta-P)
Example: A valve must pass 50 m3/h of water (G=1.0) at 2 bar pressure drop.
Kv = 50 x sqrt(1.0 / 2) = 50 x 0.707 = 35.4
A valve with rated Kv of 35.4 or higher is required.
Kv to Cv Conversion
| From | To | Formula |
|---|---|---|
| Kv | Cv | Cv = 1.156 x Kv |
| Cv | Kv | Kv = 0.865 x Cv |
The conversion factor (1.156) accounts for the unit differences: US gallons vs cubic meters, psi vs bar. These are exact relationships; no approximation.
Conversion Examples
| Kv (m3/h) | Cv (US GPM) |
|---|---|
| 10 | 11.56 |
| 25 | 28.9 |
| 50 | 57.8 |
| 100 | 115.6 |
| 250 | 289 |
| 500 | 578 |
| 1,000 | 1,156 |
Kv Values by Valve Type
| Valve Type | DN 50 | DN 100 | DN 150 | DN 200 | DN 300 |
|---|---|---|---|---|---|
| Full bore ball valve | 117 | 554 | 1,272 | 2,285 | 4,671 |
| Gate valve | 104 | 510 | 1,168 | 2,163 | 4,412 |
| Globe valve | 26 | 95 | 182 | 294 | 606 |
| Butterfly valve | 69 | 415 | 1,038 | 1,903 | 4,153 |
Where Kv Is Used
| Region/Standard | Flow Coefficient | Reference |
|---|---|---|
| North America (API, ISA) | Cv | ISA/IEC 60534 (US customary) |
| Europe (EN, DIN) | Kv | IEC 60534, EN 60534 |
| International (ISO) | Kv (preferred) or Cv | IEC 60534 supports both |
| Manufacturer datasheets | Both Kv and Cv typically listed | Dual reporting common |
Kv in Control Valve Sizing
IEC 60534 provides comprehensive sizing equations in both Cv and Kv formats. For European projects, valve datasheets, specifications, and control valve sizing calculations use Kv exclusively. When reviewing specifications from different regions, always verify which coefficient is used before sizing:
| Sizing Parameter | Cv System | Kv System |
|---|---|---|
| Flow units | US GPM | m3/h |
| Pressure units | psi | bar or kPa |
| Temperature units | degF | degC |
| Pressure recovery factor | FL (same) | FL (same) |
| Piping geometry factor | FP (same) | FP (same) |
The sizing methodology is identical; only the units differ. Using Cv values in a Kv equation (or vice versa) without conversion produces a 15.6% error; enough to cause serious over- or undersizing.
Leave a Comment
Have a question or feedback? Send us a message.